X Series Data Sheet
®
375, 500 Watt AC-DC and DC-DC DIN-Rail Converters
1
3
10074
2
Fig. 16
Cage clamp terminals. Use 0.5 to 2.5 mm 2 (AWG 20 to 12)
solid or stranded wires depending on local requirements.
The phase input (L) is internally fused; see Input Fuse and
Protection. This fuse is designed to break an overcurrent in
case of a malfunction of the converter and is not customer-
accessible.
External fuses in the wiring to one or both input lines (L and/or
N ) may be necessary to ensure compliance with local
requirements. A built-in second fuse in the neutral path is
available as option F.
A second fuse in the wiring to the neutral terminal N or option F
is needed if:
• Local requirements demand an individual fuse in each
source line
• Neutral and earth impedance is high or undefined
• Phase and neutral of the mains are not defined or cannot be
assigned to the corresponding terminals (L to phase and
N to neutral).
Models with option F: Caution! Double-pole/neutral fusing.
If the converter operates at source voltages above 250 VDC,
an external DC fuse or a circuit breaker at system level should
be installed in the phase input line L .
Caution:
• Installation must strictly follow the national safety regulations.
• Do not open this apparatus!
Protection Degree and Cleaning Agents
The protection degree of the converters is IP 20. Protective
covers over input and output terminals are available on
request; see Accessories.
Any penetration of liquid or foreign solid objects has to be
prevented, since the converters are not hermetically sealed.
Standards and Approvals
The X Series converters were approved according to IEC/
EN 50178, IEC 61010-1, IEC60950-1, UL/CSA 60950-1 2nd Ed.
The converters have been designed in accordance with said
standards for:
• Class I equipment
• Power-supply for building-in, vertical mounting on 35 mm
DIN-rail or on a wall
• Overvoltage category II (III for 110 VAC supply)
• Basic insulation between input and case, based on
250 VAC
• Double or reinforced insulation between input and output,
based on 250 VAC and 350 VDC
• Functional insulation between outputs and case
• Functional insulation between outputs
• Pollution degree 3 environment (AC-input) and degree 2
(DC input).
CB Scheme is available (SE-34628).
The converters are subject to manufacturing surveillance in
accordance with the above mentioned UL standards and with
ISO9001:2000.
See also the Declaration of Conformity (last page).
Railway Applications
All X Series converters have been designed by observing the
railway standards EN 50155 and EN 50121. All boards are
coated with a protective lacquer.
Isolation
The electric strength test is performed in the factory as routine
test in accordance with EN 50116 and IEC/EN 60950, and
should not be repeated in the field. Power-One will not honor
any warranty claims resulting from electric strength field tests.
Table 14: Isolation
Characteristic
Electric
strength
test
Factory test ³ 1 s
AC test voltage equivalent
to factory test
Insulation resistance
Input to case
and output(s)
2.8 1
2.0
>300 2
Output(s) to
case
1.4
1.0
>300 2
Output 1 to
output 2 and AUX
0.5
0.35
>100
1 In accordance with EN 50116 and IEC/EN 60950-1, subassemblies are pretested with 4.2 kVDC.
2 Tested at 500 VDC.
Unit
kVDC
kVAC
MW
BCD20021-G Rev AC1, 13-May-2013
Page 16 of 21