Data Sheet
SW/SC001/003 Series DC-DC Power Module:
December 12, 2008 18-36Vdc & 36-75Vdc Input; 3.3-15Vdc Output; 1-3.5A Output Current
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are
absolute stress ratings only, functional operation of the device is not implied at these or any other conditions in
excess of those given in the operations sections of the data sheet. Exposure to absolute maximum ratings for
extended periods can adversely affect the device reliability.
Parameter
Input Voltage (Continuous)
Transient (100ms)
Operating Ambient Temperature
(see Thermal Considerations section)
Storage Temperature
I/O Isolation Voltage (100% factory Hi-Pot tested)
Device
Symbol
Min
SW
VIN
-0.3
SC
VIN
-0.3
All
VIN, trans
-0.3
All
TA
-40
All
Tstg
-55
All
Max
Unit
80
Vdc
50
100
Vdc
85
°C
125
°C
2250
Vdc
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature
conditions.
Parameter
Operating Input Voltage
Maximum Input Current (VIN=0V to 75V, IO=IO, max)
(VIN=0V to 36V, IO=IO, max)
Inrush Transient
Input Reflected Ripple Current, peak-to-peak
(5Hz to 20MHz, 12μH source impedance; VIN=0V to
75V, IO= IOmax ; see Test configuration section)
Input Ripple Rejection (120Hz)
EMC, EN55022
Device
SW
SC
SW
SC
All
All
All
Symbol Min
Typ
Max
Unit
VIN
36
VIN
18
IIN,max
IIN,max
I2t
54
75
Vdc
27
36
Vdc
0.6
Adc
1.2
Adc
0.05
A2s
30
mAp-p
50
dB
See EMC Considerations section
CAUTION: This power module is not internally fused. An input line fuse must always be used.
This power module can be used in a wide variety of applications, ranging from simple standalone operation to being
part of complex power architecture. To preserve maximum flexibility, internal fusing is not included; however, to
achieve maximum safety and system protection, always use an input line fuse. The safety agencies require a fast-
acting fuse with a maximum rating of 3A (see Safety Considerations section). Based on the information provided in
this data sheet on inrush energy and maximum dc input current, the same type of fuse with a lower rating can be
used. Refer to the fuse manufacturer’s data sheet for further information.