datasheetbank_Logo
データシート検索エンジンとフリーデータシート

LXR1601-6G データシートの表示(PDF) - Power-One Inc.

部品番号
コンポーネント説明
メーカー
LXR1601-6G Datasheet PDF : 21 Pages
First Prev 11 12 13 14 15 16 17 18 19 20
X Series Data Sheet
®
375, 500 Watt AC-DC and DC-DC DIN-Rail Converters
Table 9: Harmonics and flicker
Phenomenon
Harmonics
Voltage fluctuation and flicker
Standards
EN 61000-3-2:2006
EN 61000-3-3 + A2:2005
Conditions
Vi = 230 V, Vo nom, Io nom
Vi = 230 V, Vo nom, Io nom
Results
Class A, D
Complied
Immunity to Environmental Conditions
Table 10: Mechanical stress and climatic
Test method
Cab Damp heat
steady state
Standard
IEC/EN 60068-2-78
MIL-STD-810D sect. 507.2
Kb Salt mist, cyclic
(sodium chloride
NaCl solution)
IEC/EN 60068-2-52
Eb Bump
(half-sinusoidal)
IEC/EN 60068-2-29
MIL-STD-810D sect. 516.3
Fc Vibration
(sinusoidal)
IEC/EN 60068-2-6
MIL-STD-810D sect. 514.3
Ea Shock
(half-sinusoidal)
IEC/EN 60068-2-27
MIL-STD-810D sect. 516.3
Fh Random vibration
broad band
digital control and
guidance
Fda Random vibration
wide band
reproducibility
high
IEC/EN 60068-2-64
IEC/EN 60068-2-35
Test conditions
Temperature:
Relative humidity:
Duration:
40 ±2 °C
93 +2/-3 %
56 days
Concentration:
Duration:
Conditions:
Storage duration:
5% (30 °C)
2 h per cycle
40 °C, 93% rel. humidity
3 cycles of 22 h
Acceleration amplitude:
Bump duration:
6000 bumps:
25 gn = 245 m/s2
11 ms
1000 in each direction
Acceleration amplitude:
Bump duration:
6000 bumps:
10 gn = 98.1 m/s2
11 ms
1000 in each direction
Acceleration amplitude and
frequency (1 Octave/min):
Test duration:
Acceleration amplitude and
frequency (1 Octave/min):
Test duration:
Acceleration amplitude:
Bump duration:
Number of bumps:
0.35 mm (10 – 60 Hz)
5 gn = 49 m/s2 (60 – 2000 Hz)
7.5 h (2.5 h each axis)
0.25 mm (10 – 60 Hz)
2 gn = 19 m/s2 (60 – 2000 Hz)
7.5 h (2.5 h each axis)
50 gn = 490 m/s2
11 ms
18 (3 in each direction)
Acceleration spectral density:
Frequency band:
Acceleration magnitude:
Test duration:
0.05 gn2/Hz
20 – 500 Hz
4.9 g n rms
3 h (1 h each axis)
Acceleration spectral density:
Frequency band:
Acceleration magnitude:
Test duration:
0.01 gn2/Hz
20 – 500 Hz
2.2 g n rms
1.5 h (0.5 h each axis)
Status
Converter
not
operating
Converter
not
operating
Converter
not operating ,
wall-mounted1
Converter
not operating ,
on DIN-rail 2
Converter
operating,
wall-mounted1
Converter
operating,
on DIN-rail 2
Converter
not operating ,
wall-mounted1
Converter
operating,
wall-mounted1
Converter
operating,
mounted on a
DIN-rail 2
1 Wall-mounted with brackets UMB-W [HZZ00618]; see Accessories
2 Fastened on a DIN-rail with 2 additional DIN-rail fixing brackets DMB-EWG; see Accessories. This also covers wall-mounting with
brackets, because wall mounting performs better in vibration test.
Temperatures
Table 11: Temperature specifications, valid for an air pressure of 800 - 1200 hPa (800 - 1200 mbar)
Model
Standard models -6
Unit
Characteristics
Conditions
min
TA Ambient temperature
Converter
–40
TC Case temperature
operating1
–40
TS Storage temperature
Not operating
–40
max
60
°C
902
100
1 See Thermal Considerations
2 See table 4 and 5 Po derating
BCD20021-G Rev AC1, 13-May-2013
Page 13 of 21
www.power-one.com