3 / // / 30-GC6NLT1
APPLICATION DATA
// Engine
Manufacturer
Model
Type
Arrangement
Displacement: L (in3)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
Engine Governor
Maximum Power (NG): kWm (bhp)
Maximum Power (LP): kWm (bhp)
Speed Regulation
Air Cleaner
// Liquid Capacity (Lubrication)
Total Oil System: L (gal)
Engine Jacket Water Capacity: L (gal)
System Coolant Capacity: L (gal)
// Electrical
Electric Volts DC
Cold Cranking Amps Under -17.8 °C (0 °F)
// Fuel Inlet
Fuel Supply Connection Size
Fuel Supply Pressure: mm H20 (in. H20)
// Fuel Consumption (NG-1000 BTU/ft3 / LP-2500 BTU/ft3)
GM
3.0L
4-Cycle
4-Inline
3 (181)
10.2 (4)
9.1 (3.6)
9.25:1
1,800
Bosch
37.9 (50.8)
38.4 (51.5)
C/F
Dry
At 100% of Power Rating: m3/hr (ft3/hr)
At 75% of Power Rating: m3/hr (ft3/hr)
At 50% of Power Rating: m3/hr (ft3/hr)
NG
10.2 (361)
7.7 (270)
5.4 (189)
// Cooling - Radiator System
Ambient Capacity of Radiator: °C (°F)
50 (122)
Maximum Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
0.12 (0.5)
64.4 (17)
Heat Rejection to Coolant: kW (BTUM) 25.3 (1,436)
Heat Radiated to Ambient: kW (BTUM) 15.6 (886)
Fan Power: kW (hp)
2.2 (3)
LPG
4.5 (159)
3.4 (120)
2.4 (84)
2.2 (3)
// Air Requirements
4.9 (1.3)
3.8 (1)
14.8 (3.9)
12
925
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
Cooled Unit: *m3/min (SCFM)
Remote Cooled Applications;
Air Flow Required for Dissipation
of Radiated Gen-set Heat For a
Max of 25 °F Rise: *m3/min (SCFM)
2.7 (94.3)
81.6 (2,882.39)
56.6 (1,998)
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
// Exhaust System
3/4” NPT
178–279 (7–11)
Gas Temp. (Stack): °C (°F)
Gas Volume at Stack
Temp: m3/min (CFM)
Maximum Allowable
Back Pressure: kPa (in. H 0)
2
704.4 (1,300)
8.6 (304.53)
10 (40)