Processing and Connecting Cable/Conduit
The following procedures are recommended for mounting and wiring
the indicator unit securely.
In order to ensure IP67, use OMRON’s SC-#M and Nippon Flex’s
ABS-08Pg13.5 and ABS-12 Pg13.5 Connectors.
Recommended cable: UL2464-type cable that is 20 to 18 AWG (0.5
to 1.0 mm2) in size and has seven conductors
If the 1/2-14NPT is used, cover the cable and conduit end with seal-
ing tape in order to ensure IP67. Tighten the connector to a torque of
1.77 to 2.16 N·m.
Connect the indicator unit after connecting the seven-conductor
cable.
Cable Connection Example
1. Connect the wires to the terminals in the order shown below for
wiring efficiency.
Tighten each wired terminal clockwise to a torque of 0.59 to
0.78 N·m.
Terminal no.
E1
E2
31
12
23 (21)
24 (22)
Lp (mm)
30±2
35±2
45±2
55±2
65±2
70±2
90±2
Lv (mm)
80±2
75±2
60±2
50±2
45±2
35±2
50±2
a (mm)
8±1
Properly attach and securely tighten the provided conduit cap to the
unused conduit opening when wiring the D4BL.
Twist the wire two or three times and make sure that no bare wire
exists outside the terminal when tightening the terminal.
2. The insulation sheath of the seven-conductor cable must come
into contact with the wall of the conduit mouth, side A or side B.
Insulation sheath edge
Maintenance and Repairs
Contact your OMRON representative for any repair or maintenance
work on the D4BL. The D4BL must not be maintained or repaired by
any unauthorized party.
Others
Do not touch the solenoid because the solenoid radiates heat while
power is being supplied.
D4BL
D-147